Insulation Resistance Measurement

MIC-10k1

  • » Auto ranging, Trms AC voltage and current measurement
  • » Resistance, Capacitance, Frequency,mV ,mA ,Diode and Continuity measurement facility
  • » Select, Range, Hold/Light, Relative, Hz/Duty, Min/Max functions incorporated
  • » Robust, Rugged and dust proof casing
  • » CAT IV,600V/ IP-54 protected
  • » IEC 61010-1-2010 compliance
  • Description

  • M63 is specially designed industrial grade Trms digital multimeter in our research laboratory & manufactured under stringent manufacturing process for wide range of applications like Power generation, Power distribution, Power transmission, Steel Industries, Cement Industries, Mining Industries, Power Electronics Industries, Heavy Engineering Industries, and Defense Sector & Aviation Sector. M63 is a high performance multimeter with high safety, linearity and reliability. Excellent noise immunity to disturbances from energized power lines, with CAT IV & IP-54 protection.



MIC-5050

  • » Auto ranging, Trms AC voltage and current measurement
  • » Resistance, Capacitance, Frequency,mV ,mA ,Diode and Continuity measurement facility
  • » Select, Range, Hold/Light, Relative, Hz/Duty, Min/Max functions incorporated
  • » Robust, Rugged and dust proof casing
  • » CAT IV,600V/ IP-54 protected
  • » IEC 61010-1-2010 compliance
  • Description

  • M63 is specially designed industrial grade Trms digital multimeter in our research laboratory & manufactured under stringent manufacturing process for wide range of applications like Power generation, Power distribution, Power transmission, Steel Industries, Cement Industries, Mining Industries, Power Electronics Industries, Heavy Engineering Industries, and Defense Sector & Aviation Sector. M63 is a high performance multimeter with high safety, linearity and reliability. Excellent noise immunity to disturbances from energized power lines, with CAT IV & IP-54 protection.



MIC-5010

  • » Insulation resistance measurement:
  • - measurement voltage any in the range of 50…1000 V at 10 V and 1000...5000 V at 25 V resolution,
    - continuous indication of measured insulation resistance or leakage current,
    - automatic discharge of measured object capacitive voltage after the end of insulation resistance measurement,
    - acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
    - metered T1 , T2 and T3 test times for measuring one or two absorption coefficients from the range of 1…600 s,
    - adjustable measuring time to 99'59'’,
    - polarization index (PI) and dielectric absorption ratio (DAR) measurement,
    - indication of actual test voltage during measurement,
    - 1.2 mA and 3 mA test current,
    - step voltage insulation resistance measurement (SV),
    - Dielectric Discharge calculation (DD),
    - protection against measuring live objects,
    - measurements with test leads up to 20 m
  • » Digital filters function for measurements in high noise enviroment (10 s, 30 s , 60 s).
  • » Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557-4 with current > 200 mA.
  • » Adjustable limits for measured resistance RISO and RCONT.
  • » Measurement of leakage current during insulation resistance testing.
  • » Measurement of capacitance during the measurement of RISO.
  • » DC and AC voltage measurement in the range of 0…600 V.
  • » 990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR adapter) or through a USB cable.
  • » Power supply from battery packs, low battery warning indicator, built-in fast charger.
  • » Keyboard and display backlit.
  • Specification

  • Insulation resistance measurement (two-lead)

    Measurement range acc. to IEC 61557-2: 50k…15,0 TΩ (IISOnom = 1,2 mA or 3 mA)

    Range Resolution Accuracy
    0,0...999 kΩ 1 kΩ ±(3% m.v. + 10 digits)
    1.00...9,99 MΩ 0,01 MΩ
    10.0...99,9 MΩ 0,1 MΩ
    100...999 MΩ 1 MΩ
    1.00...9,99 GΩ 0,01 GΩ
    10.0...99,9 GΩ 0,1 GΩ
    100...999 GΩ 1 GΩ ±(3.5% m.v. + 10 digits)
    1.00...9,99 TΩ 0,01 TΩ ±(7.5% m.v. + 10 digits)
    10.0...15,0 TΩ 0,1 TΩ ±(10% m.v. + 10 digits)

    Values of measured resistance depending on measurement voltage

    Voltage UISO Measurement range
    250 V 500 GΩ
    500 V 1.00 TΩ
    1000 V 2.00 TΩ
    2500V 5.00 TΩ
    5000V 15.0 TΩ

     

    Measurement of leakage current

     

    Range Resolution Accuracy
    0…ILmax m, µ, n [A] Calculated basing on
    resistance measurements

    · ILmax – maximum current at short circuit of leads,
    · resolution and units result from the measurement range of individual insulation resistance.

    Step voltage insulation resistance measurement

    Target voltage Measurement
    voltage sequence
    1 kV 200, 400, 600, 800, 1000 V
    2.5 kV 0.5, 1, 1.5, 2, 2.5 kV
    5 kV 1, 2, 3, 4, 5 kV

    · duration of each "step" adjustable from 30s to 5mins
    · measurement result for each voltage step is stored in memory

    Continuity measurement of protective connections and equipotential bonding with 200 mA current
    Measurement range acc. to EN 61557-4: 0,12...999 Ω

    Range Resolution Accuracy
    0.00...19.99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
    120.0...199.9 Ω 0,1 Ω
    200...999 Ω 1 Ω ±(4% m.v. + 3 digits)

    · Voltage on open terminals: 4...24 V
    · Output current at R < 2 Ω: Imin > 200 mA (ISC: 200...250 mA)
    · Compensation of test lead resistance
    · Current flowing in both directions, mean value of resistance is displayed

    Capacity measurement

    Range Resolution Accuracy
    1...999 nF 1 nF ±(5% m.v. + 5 digits)
    1.00...49.99 µF 0.01 µF

    · Capacity measurement result is displayed after the RISO measurement

    DC and AC voltage measurement

    Range Resolution Accuracy
    0.0...29.9 V 0.1 V ±(2% m.v. + 20 digits)
    30.0...299.9 V 0.1 V ±(2% m.v. + 6 digits)
    300...600 V 1 V ±(2% m.v. + 2 digits)

     

    The acronym “m.v.” stands for a “measured reference value”.




MIC-5000

    Description

  • Digital insulation resistance meter MIC-5000 is intended for direct measurements of insulation resistance in power cables, transformers, electric motors and other power devices and equipment. Additionally, the device enables measurement of DC and AC voltages as well as low voltage measurement of low resistances. All test terminals of the instrument are fitted with a circuitry protecting the device from damage should the mains voltage appear on the input. The instrument was designed and built in compliance with EN IEC 61557 standard.
  • Specification

    The most important features of MIC-5000 are:

    Insulation resistance measurement:

    • test voltage selection between 250...5000 V in 50 V intervals, or predefined 250, 500, 1000, 2500, 5000 V,
    • on-line insulation resistance measurement or leakage current,
    • automatic discharge of tested object’s capacitance after measurement of insulation resistance,
    • direct measurement of one or two absorption coefficients,
    • acoustic determination of 5 seconds time intervals that facilitates to take time characteristics during insulation resistance measurement,
    • saving measured value of test voltages and selected times T1, T2 and T3 ranging from 1... 600 seconds for the measurements of one or two absorption coefficients (DAR, PI or Ab1, Ab2),
    • indicator of the actual test voltage value during a measurement,
    • protection against live objects.

    AC/DC voltage measurement in range 0...600 V.

    Memory for 999 measurement results with an ability to transfer the datato a PC.

    Automatic selection of measurement ranges.

    Powered by rechargeable battery pack:

    • included with the device an external power supply for automatic battery charging to ensure prolonged battery life and optimal working conditions,
    • battery status indicator.

    AUTO-OFF function.

    Meter meets the requirements of the standard EN 61557.

    Electric security:

    • type of insulation: double, according to EN 61010 - 1 and IEC 61557
    • measurement category: CAT III 600 V acc. to EN 61010 - 1
    • measurement category for terminals and circuit 5 kV: interpolated III 5000 V
    • protection class acc. to EN 60529: IP54

    Rated operational conditions:

    • operating temperature: -10...+50°C,
    • test voltage accuracy (Robc[Ω]≥1000*Un[V]): -0...+10% of the set value,
    • voltage fluctuation due to temperature changes better than: 0,2%/°C,
       

    Converter output current:

    • min. 1,0 mA for rated test voltage
    • 1,0...3,0 mA for 2500 V
    • 1,0...1,4 mA for 5000 V
    • measurement rate: approx. 1 measure/second
    • quality standard: ISO 9001

    Other technical data:

    • - power supply: Ni-MH battery pack
    • - power supply adaptor: 100...240 V
    • - minimum measurement time 5 kV/1 mA according to
    • EN 61557 (5 s/25 s) 5 h or 600 measurements

     

    Time to auto-off:

    • mode RISO/IL depends on T2 or T3 (T2/T3 + 300 seconds) settings
    • other modes 300 seconds

    Insulation resistance measurement

    • test voltage can be set in the range between 250 V and 5000 V with 50 V intervals
    • test voltage accuracy (Robc [Ω] ≥ 1000*UN [V]): 0 + 10% of the set value
    • voltage fluctuation due to temperature changes - better than 0,2% / °C
    • measurement times T1, T2 i T3 for absorption coefficient measurement selected from the range between 1 sec and 600 sec with accuracy ± 1 sec

     

    measurement range according to PN-EN 61557 - 2: RISOmin...5,0 TΩ; RISOmin=UISOnom/1 mA

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 20 digits)
    1,000...9,999 MΩ 0,001 MΩ
    10,00...99,99 MΩ 0,01 MΩ
    100,0...999,9 MΩ 0,1 MΩ
    1,000...9,999 GΩ 0,001 GΩ
    10,00...99,99 GΩ 0,01 GΩ
    100,0...999,9 GΩ 0,1 GΩ
    1,000...5,000 TΩ 0,001 TΩ

    • for measurements of limited converter current, the accuracy is not specified.

    Minimum insulation resistance measured without limited converter current

    Test voltage Range
    250 V 250 kΩ
    500 V 500 kΩ
    1000 V 1,0 MΩ
    2500 V 2,5 MΩ
    5000 V 5,0 MΩ

     

    DC voltage measurement

     

    Range Resolution Accuracy
    0...600 V 1 V ±(3% m.v. + 2 digits)

    AC voltage measurement 
    50 Hz (sinusoidal shape with harmonic contents < 2%)

    Range Resolution Accuracy
    0...600 V 1 V ±(3% m.v. + 2 digits)

    „m.v.” - measured value.

     

    Leakage current reading

    Range Resolution Accuracy
    0...Ipmax depending on range -ΔI-, +ΔI+

    Ipmax - maximum converter current 1,2 ± 0,2 mA,
    ΔI-, +ΔI+ - current reading accuracy calculated using the following formula:

     

    UISO - test voltage
    R - displayed insulation resistance value
    ΔR - resistance measurement defined for a particular measurement




MIC-2510

    Description

    • INSULATION RESISTANCE MEASUREMENT UP TO 2 TΩ IN ACCORDANCE WITH IEC 61557 - 2 FULL CAPTURE AND RECORDING OF MEASUREMENT CONDITIONS Capability of wireless transmission of the data from memory to a PC - ADDITIONALLY ORDER THE WIRELESS USB INTERFACE! Insulation resistance measurement:
    • » selectable measurement voltage 100, 250, 500, 1000 V or any in the range of 50 - 2500 V at 10 V resolution,
    • » continuous indication of measured insulation resistance or leakage current,
    • » automatic discharge of measured object capacitive voltage after the completion of insulation resistance measurement,
    • » acoustic signaling of 5 seconds intervals to facilitate capturing time characteristics,
    • » metered T1, T2 and T3 test times from the range of 1...600 s for measuring one or two absorption coefficients (DAR, PI or Ab1, Ab2),
    • » capability of automatic measurement of multi-wire cables with the additional AutoISO-2500 adapter,
    • » indication of actual test voltage during measurement,
    • » protection against measuring live objects.
    • Continuity measurement of protective connections and equipotential bonding in accordance with EN 61557 - 4 with current > 200 mA. Circuit continuity and resistance measurement at low voltage.
    • » circuit resistance measurement ( < 999 ) with current < 15 mA,
    • » quick acoustic signaling for a circuit of resistance lower than 10,
    • » compensation (automatic zero) of test lead resistance.
    • Measurement of leakage current during insulation resistance testing.
      Measurement of capacity during the measurement of RISO.
      Continuous measurement of surrounding temperature with the capability of recording results in memory.
      DC and AC voltage measurement in the range of 0-600 V.
      990 cells of memory (11880 records) with the capability of wireless data transmission to a PC (with the USB-OR-1 adapter) or through a USB cable.
      Power supply from battery packs.

Specification

Electrical safety:

  • » type of insulation: double, in acc. with EN 61010 - 1 and IEC 61557
  • » measurement category: IV 600 V (III 1000 V) in acc. with EN 61010 - 1
  • » case protection rating in acc. with EN 60529: IP54

Other technical specifications:

  • » power supply of the meter: SONEL L-1 NiMH 9.6 V battery pack
  • » weight of the meter: approx. 1,3 kg
  • » dimensions: 260 x 190 x 60 mm
  • » display: LCD segment display
  • » measurement results memory: 990 cells, 11880 records
  • » transmission of measurement results: USB or wireless interface

Insulation resistance measurement (two-lead)

Measurement range acc. to IEC 61557 - 2 for RISOmin=UISOnom/IISOmax...2 TΩ (IISOmax=1 mA)

Range Resolution Accuracy
0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 20 digits)
1,000...9,999 MΩ 0,001 MΩ
10,00...99,99 MΩ 0,01 MΩ
100,0...999,9 MΩ 0,1 MΩ
1,000...9,999 GΩ 0,001 GΩ
10,00...99,99 GΩ 0,01 GΩ
100,0...999,9 GΩ 0,1 GΩ
1,000...2,000 TΩ 0,001 TΩ

Values of measured resistance depending on measurement voltage

Voltage UISO Measurement range
50 V 50 GΩ
100 V 100 GΩ
250 V 250 GΩ
500 V 500 GΩ
1000 V 1,00 TΩ
2500 V 2,00 TΩ

Measurement of insulation resistance with the AutoISO-2500 adapter

Range Resolution Accuracy
0,0...999.9 kΩ 0,1 Ω ±(3% m.v. + 20 digits)
of the meter + max 1%
of AutoISO-2500
uncertainty
1,000...9.999 MΩ 0,001 MΩ
10,00...99,99 MΩ 0,01 MΩ
100,0...999,9 MΩ 0,1 MΩ
1,000...9,999 GΩ 0,001 GΩ
10,00...99,99 GΩ 0,01 GΩ
100,0...400,0 GΩ 0,1 GΩ ±(3% m.v. + 20 digits)
of the meter + max 5%
of AutoISO-2500 uncertainty

Values of measured resistance depending on measurement voltage

Voltage UISO Measurement range
100 V 100 GΩ
250 V 250 GΩ
500 V, 1000 V, 2500 V 400 GΩ

Continuity measurement of protective connections and equipotential bonding with 200 mA current

Measurement range acc. to EN 61557 - 4: 0.10...999 Ω

Range Resolution Accuracy
0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
20,0...199,9 Ω 0,1 Ω
200...999 Ω 1 Ω ±(4% m.v. + 3 digits)
  • » Voltage on open terminals: 8...16 V
  • » Output current at R <2 Ω: ISC >200 mA
  • » Compensation of test lead resistance
  • » Current flowing in both directions, mean value of resistance is displayed

Resistance measurement with low current

Range Resolution Accuracy
0,0...199,9 Ω 0,1 Ω ±(2% m.v. + 3 digits)
200...999 Ω 1 Ω ±(4% m.v. + 4 digits)
  • » Voltage on open terminals: 8...16 V
  • » Output current > 10 mA
  • » Acoustic signal for measured < 10 Ω ± 10%
  • » Compensation of test lead resistance

Capacity measurement

Display range Resolution Accuracy
1...999 nF 1 nF ±(5% m.v. + 10 digits)
1,00...9,99µF 0,01µF
  • » Capacity measurement result is displayed after the RISO measurement

Temperature measurement

Range Resolution Accuracy
-40,0...99,9°C 0,1°C ±(3% m.v. + 8 digits)
-40,0...221,8°F 0,1°F ±(3% m.v. + 16 digits)
  • » measurement with the use of an external probe

DC and AC voltage measurement

Range Resolution Accuracy
0...600 V 1 V ±(3% m.v. + 2 digits)

Frequency range : 45...65 Hz

 



MIC-2505

    Description

  • INSULATION RESISTANCE MEASUREMENT UP TO 2T IN ACCORDANCE WITH IEC 61557 - 2

    Insulation resistance measurements:

    • » selectable measurement voltage 500, 1000 V or 2500 V,
    • » continuous indication of measured insulation resistance or leakage current value,
    • » automatic discharge of measured object capacitive voltage after the completion of insulation resistance measurement,
    • » acoustic signaling of 5 seconds time intervals to facilitate capturing time characteristics,
    • » metered T1, T2 and T3 test times (15,60 and 600 s or 30,60 and 600 s) for measuring two absorption coefficients (DAR, PI, Ab1, Ab2),
    • » indication of actual test voltage during measurement,
    • » protection against measuring live objects.

    Insulation resistance measurement method for two-and three-wire.

    Measurement of leakage current during insulation resistance testing.

    DC and AC voltage measurement in the range of 0…600 V.

    Power supply from battery packs.

    The instruments meet the requirements of the EN 61557 standard.



MIC-30

    Description

  • Insulation resistance measurement:

    • » selected test voltage: any voltage in the 50...1000 V range with 10 V step,
    • » automatic measurement in sockets with the UNI-Schuko adapter with possibility of configuring pairs of measured cables,
    • » continuous indication of insulation resistance or leakage current,
    • » automatic discharge of capacitance of tested object after the insulation resistance measurement,
    • » acoustic signalling of five-second periods to facilitate obtaining time characteristics,
    • » measured test times T1, T2 i T3 to measure one or two absorption coefficients in the 1... 600 sec. range,
    • » indication of actual test voltage during the measurement,
    • » protection against measuring live objects,
    • » three-lead measurement.

    Continuity measurement of protective and equipotential conductors according to EN 61557 - 4 with the >200 mA current

    Low-voltage circuit continuity and resistance measurement:

    • » circuit resistance measurement (<1999 Ω ) with the <15 mA current,
    • » quick sound signal if circuit resistance is below 30Ω.

    Leakage current measurement.

    Capacitance measurement during the RISO measurement

    Measurement of alternating and direct voltages in the 0...600 V range.

    990 memory cells and wireless data transmission to a computer using the USB - OR-1 adapted.

    Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage.

    Meters conform to EN 61557.

    Specification

    Possible measurements:

    • » Measurements according to EN 50160
    • » Voltage L1, L2, L3, N-PE (five inputs, compiles with EN 61000 - 4-30, class A)
      - average, minimum, maximum and instantaneous values, range to 690 V, ability to work with voltage transformers,
    • » Current L1, L2, L3, N (four inputs)
      - average, minimum, maximum and instantaneous values, measurement current with range to 3 kA (depends on used clamp), ability to work with current transformers,
    • » Crest factor for voltage and current,
    • » Frequency from 40 Hz to 70 Hz (compiles with EN 61000 - 4-30, class A),
    • » Active, reactive, distortion, apparent power, including the type of reactive power (capacitive, inductive),
    • » Power recording:
      - Budeanu method,
      - IEEE 1459,
    • » Active, reactive, apparent energy,
    • » Power factor, cosφ, tgφ,
    • » K factor (transformer overload caused by the harmonics),
    • » Up to 50th harmonics for voltage and current (compiles with EN 61000 - 4-7, class I),
    • » Total Harmonic Distortion (THD) for voltage and current,
    • » Short-term (PST) and long-term (PLT) flicker (compiles with EN 61000 - 4-15, class A),
    • » Unballace of Voltage (compiles with EN 61000 - 4-30, class A) and current,
    • » Voltage dips, swells and interruption registration including oscillograms (compiles with EN 61000 - 4-30, class A),
    • » Current events registration including oscillograms,
    • » Current and voltage oscillograms registration after each averaging period.
    Specification Range Resolution Accuracy

    AC
    voltage
    (TRMS)

    - 0,0…690,0 V 0,01 % Un ±0,1% Un
    Crest
    Factor
    Voltage

    1,00…10,00
    (≤1,65 for
    voltage 690 V)

    0,01 ±5%
    Current 1,00…10,00
    (≤3,6 Inom)
    0,01 ± 5% m.v.
    AC
    current
    TRMS
    - depends on
    the clamp*
    0,01 % of nominal range ±0,1% of nominal
    range
    (add clamps
    accuracy)
    Frequency - 40,00...70,00 Hz 0,01 Hz ±0,01 Hz
    Active,
    reactive,
    apparent
    power
    and
    distortion
    - depends
    of configuration
    (transformers,
    clamp)
    up to 4
    decimal places
    depends
    on configuration
    (transformers,
    clamp)
    Active, reactive apparent energy - depends
    of configuration
    (transformers,
    clamp)
    up to 4
    decimal places
    the same
    as above
    cosφ
    and Power
    Factor (PF)
    - 0,00...1,00 0,01 ±0,03
    tgφ - 0,00...10,00 0,01 depends on Active
    and Reactive
    power accuracy
    Harmonics Voltage same as for AC
    voltage TRMS
    same as for
    AC voltage TRMS
    ±5% Uh
    for Uh ≥ 1% Un
    ±0,05% Un
    for Uh < 1% Un
     
    Current same as for AC
    current TRMS
    same as for
    AC current TRMS
    ± 5% Ih 
    for Ih ≥ 3% In
    ± 0,15% In
    for Ih < 3% In
    Total
    Harmonics
    Distortion
    Voltage 0,0..100,0% 0,1% ±5%
    Current ±5%
    Harmonics
    active
    and
    reactive
    power
    - depends on configuration
    (transformers,
    clamp)
    depends
    on current
    and voltage
    minimum value
    -

    Angle
    between
    voltage
    and current
    harmonics

    - -180,0…+180,0o 0,1o ±(h x 1o)
    K-Factor - 1,0...50,0 0,1 ±10%
    Flicker - 0,20...10,00 0,01 ±5%
    Unbalance Voltage and Current 0,0...20,0% 0,1% ±0,15%
    (absolute error)

    *Clamp F-1/F-2/F-3:0..3000 A (10000 Ap-p) *Clamp C-4: 0..1000 A (3600 Ap-p)*Clamp C-5: 0..1000 A (3600 Ap-p)*Clamp C-6: 0..10 A (36 Ap-p) (without current transformers)

    Sonel Analysis 1.0

    „SONEL Analysis” software is an application used to work with PQM-701 power quality analyzer. It enables:

    • » analyzer configuration,
    • » reading data from the analyzer,
    • » network parameters check in real time,
    • » data deleting in the analyzer,
    • » data presentation in tables,
    • » data presentation in diagrams,
    • » data analysis according to EN 50160 or according to user defined conditions,
    • » independent service of multiple analyzers,
    • » software upgrade through the Internet.

    Analyzer configuration

    The software enables configuration of all analyzer’s parameters. The configuraton is made on the PC computer and later transfered to the analyzer. The configuration settings can be stored on hard drive or other data storage devices to be used later.The software enables the configuration of:

    • » wthe choice of Measurement Points and memory assigment to each Measurement Point,
    • » analyzer time settings,
    • » keyboard lock,
    • » PIN code security,
    • » averaging time setting,
    • » choice of current and voltage transformers,
    • » trigger mode choice (immidiately, after an event or according to the scheduler),
    • » choice of clamp’s type, setting of additional parameters registration in N and PE channels,
    • » choice of network type, for which the analyzer will be used.

    The analyzer has four independent Measurement Points. Each Measurement Point can be set individually to perform four different types of registration without need to change analyzer’s configuration.

    For each Measurement Point the following settings can be made:

    • » cwheather the analyzer shall work according to EN 50160 or according to user defined conditions,
    • » for each registration user can define, which network parameters shall be registered,
    • » for each parameter user can define wheather the analyzer shall register average, minimum, maximum or instantaneous values,
    • » the limits beyond which the analyzer will record the event can be defined.

    Recent data reading

    “SONEL Analysis” software enables reading of selected parameters and their graphic presentation in real time.These parameters are measured independently of the registration saved on the memory card. User can check:

    • » wvoltage and current diagrams (oscilloscope),
    • » diagrams of voltage and current in time function,
    • » scope phasor,
    • » different parameters values,
    • » harmonics and harmonics’ power.

     

    Data analysis

    With “SONEL Analysis” software user can read data stored on the memory card and analyze them. Data from the analyzer can be stored on hard drive and be used later. This feature enables data archiving.

    The user can analyze the data from the device.There is a choice of:

    • General – all data are shown with dots (Measurements, Events and Oscillograms),
    • Measurements – all measured values registered in averaging time are shown with dots (voltage, frequency, etc.),
    • Events – all detected events are shown with dots (dips, swells, interruptions, etc.).


MIC-10

    Description

  • » Insulation resistance measurement:
    - selected test voltage: 50, 100, 250, 500, 1000 V,
    - continuous indication of insulation resistance or leakage current,
    - automatic discharge of capacitance of tested object after the insulation resistance measurement,
    - acoustic signalling of five-second periods to facilitate obtaining time characteristics,
    - indication of actual test voltage during the measurement,
    - protection against measuring live objects,
    - three-lead measurement.
  • » Continuity measurement of protective and equipotential conductors according to EN 61557 - 4 with the >200 mA current
  • » Low-voltage circuit continuity and resistance measurement:
    - circuit resistance measurement (<1999 ) with the <15 mA current,
    - quick sound signal if circuit resistance is below 30Ω.
  • » Capacitance measurement during the RISO measurement
  • » Measurement of alternating and direct voltages in the 0...600 V range.
  • » Power supply: 4 AA disposable or rechargeable batteries, monitoring of power supply voltage.
  • » Meter conform to EN 61557.
  • Specification

    Electric safety:

    • » type of insulation: double, according to EN 61010 - 1 and IEC 61557
    • » measurement category: IV 600 V (III 1000 V) according to EN 61010 - 1
    • » protection class acc. to EN 60529: IP67

    Other technical specifications:

    • » power suply: 4 alkaline batteries or or battery package Ni-MH
    • » weight: ~1 kg
    • » dimentions: 220 x 100 x 60 mm

    Insulation resistance measurement

    Measuring range according to EN 61557 - 2 for UN=50 V: 50 kΩ...250,0 MΩ

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 8 digits)
    1,000...9,999 MΩ 0,001 MΩ
    10,0...99,99 MΩ 0,01 MΩ
    100,0...250,0 MΩ 0,1 MΩ

    Measuring range according to EN 61557 - 2 for UN=100 V: 100 kΩ...500,0 MΩ

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 8 digits)
    1, 000...9,999 MΩ 0,001 MΩ
    10,0...99,99 MΩ 0,01 MΩ
    100,0...500,0 MΩ 0,1 MΩ

    Measuring range according to EN 61557 - 2 for UN=250 V: 250 kΩ...2,000 GΩ

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 8 digits)

    1,000...9,999 MΩ

    0,001 MΩ

    10,0...99,99 MΩ

    0,01 MΩ
    100,0...999,0 MΩ 0,1 MΩ
    1,000...2,000 GΩ 0,001 GΩ

    Measuring range according to PN-EN 61557 - 2 for UN=500 V: 500 kΩ...5,00 GΩ

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 8 digits)
    1,000...9,999 MΩ 0,001 MΩ
    10,00...99,99 MΩ 0,01 MΩ
    100,0...999,0 MΩ 0,1 MΩ
    1,000...5,000 GΩ 0,001 GΩ ±(4% m.v. + 6 digits)

    Measuring range according to EN 61557 - 2 for UN=1000 V: 1000 kΩ...10,00 GΩ

    Range Resolution Accuracy
    0,0...999,9 kΩ 0,1 kΩ ±(3% m.v. + 8 digits)
    1,000...9,999 MΩ 0,001 MΩ
    10,00...99,99 MΩ 0,01 MΩ
    100,0...999,0 MΩ 0,1 MΩ
    1,000...5,000 GΩ 0,001 GΩ ±(4% m.v. + 6 digits)
    5,00...10,00 GΩ 0,01 GΩ

    Continuity measurement of protective and equipotential conductors with the 200 mA current

    Measuring range according to EN 61557 - 4: 0,10...1999 Ω

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
    20,0...199,9 Ω 0,1 Ω
    200...1999 Ω 1 Ω

    ±(4% m.v. + 3 digits)

    • » Voltage on open terminals: <8 V
    • » Output current at R <2 Ω: ISC >200 mA: ISC >200 mA
    • » Compensation of test leads’ resistance
    • » Unidirectional current flow

    Low-voltage and resistance measurement

    Range Resolution Accuracy
    0,0...199,9 Ω 0,1 Ω ±(3% m.v. + 3 digits)
    200...1999 Ω 1 Ω
    • » Voltage on open terminals: <8 V
    • » Current for closed terminals 5 mA < ISC < 15 mA
    • » Sound signal and green LED on when measured resistance < 30 Ω ± 50%
    • » Compensation of test leads’ resistance,

    Capacitance measurements

    Range Resolution Accuracy
    1...999 nF 1 nF ±(5% m.v. + 5 digits)
    1,00...9,99µF 0,01µF
    • » Capacitance value displayed during the RISO measurement
    • » For test voltages below 100 V and measured resistance below 10 MΩ, unspecified capacitance measurement error

    Measurement of alternating and direct voltage

    Range Resolution Accuracy
    0,0...299,9 V 0,1 V ±(2% m.v. + 6 digits)
    300...600 V 1 V ±(2% m.v. + 2 digits)
    • » Frequency range: 45...65 Hz



MIC-2

    Description

  • Digital insulation meter MIC-2 automatically select insulation measurements range at 250 and 500 V test voltages. This insulation meter is suited for insulation resistance measurements of electric installations, motors and other electric devices. MIC-2 can also be used to measure voltage up to 600 V AC and resistance up to 1999. Instrument is easy to use, professional tool in small and incredibly ergonomic case.
  • Specification

    Insulation resistance measurement:

    • » the measurement voltage is selected between the two values 250 V or 500 V,
    • » on-line insulation resistance measurement,
    • » automatic discharge of tested object’s capacitance after measurement of insulation resistance,
    • » acoustic determination of 5 seconds time intervals that facilitates to take time characteristics during insulation resistance measurement,
    • » protection against live objects.

    Low voltage resistance measurement in range 0...2000 Ω:

    • » current measurement <10 mA with resolution 0.1 Ω,
    • » quick acoustic signalling (beeper) for circuit resistance below 10 Ω.

    Pomiar napięć stałych i przemiennych w zakresie 0...600 V:

    • » samoczynne wykrywanie rodzaju napięcia (stałe/przemienne).

    AC/DC voltage measurement in range 0...600 V:

    • » automatic detection AC/DC voltage.

    Autoranging.

    Suitable for 50 Hz and 60 Hz network.

    Backlit display.

    „AUTO-OFF” function.

    Meter meets the requirements of the standard EN 61557.

    Insulation resistance measurement:
    UISO=250 V
    Measurement range: IEC 61557 - 2: 250 kΩ...1000 MΩ

    Range Resolution Accuracy
    1...249 kΩ 1 kΩ not specified
    250...1999 kΩ 1 kΩ ± (3% m.v. + 8 digits)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...1000 MΩ 1 MΩ

     

    UISO=500 V
    Measurement range: IEC 61557 - 2: 500 kΩ...1999 MΩ

    Range Resolution Accuracy
    1...499 kΩ 1 kΩ nie definiowany
    500...1999 kΩ 1 kΩ ± (3% m.v. + 8 digits)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...1999 MΩ 1 MΩ

    Resistance measurement:

    Range Resolution Accuracy
    0,0...199,9 Ω 0,1 Ω ±(4% m.v. + 3 digits)
    200...1999 Ω 1 Ω
    • » continuous audible signal for R < 10 Ω
    • » measurement current (with open terminals for Ubat > 3.0 V): < 10 mA
    • » max voltage on open terminals: 4...24 V
    • » max interference voltage for which measurement is still possible: +7 V/-1 V DC, 5 V AC

    AC/DC voltage measurement

    Range Resolution Accuracy
    0...600 V 1 V ±(3% m.v. + 2 digits)

    „m.v.” - measured value



MPI-530

    Description

    • MPI-530 meter is a multi-functional instrument for electric shock protection measurements including the option of various methods for measuring earthing and earthing resistance. Additionally the meter enables its user to analyse power supply parameters, records and displays them on its screen. The instrument automatically measures the insulation resistance in a socket and in 3 -, 4 - and 5-wire cables when used with AutoISO-1000C adapter. Measurement results may be continuously verified, depending on user’s demand or according to binding regulations. Memory of the instrument may store tens of thousands of measurements allowing users to store them in a structure of a protocol and describe individual measurement points.

    Specification

  • Measurement of short circuit loop impedance ZL-PE, ZL-N, ZL-L
    Test current: 23/40 A; measuring range acc. to IEC 61557: 0,13...1999,9 Ω
    (for 1.2 m test lead):

    Display range Resolution Accuracy
    0,000...19,999 Ω 0,001 Ω ±(5% m.v. + 3 digits)
    20,00...199,99 Ω 0,01 Ω
    200,0...1999,9 Ω 0,1 Ω

    Rated voltage: 95...270 V (for ZL-PE and ZL-N) and 95...440 V (for ZL-L)
    Frequency: 45...65 Hz;

    Measurement of short circuit loop impedance ZL-PE in RCD mode
    Test current: 15 mA, measuring range acc. to IEC 61557: 0,50...1999 Ω

    Display range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(6% w.m. + 10 digits)
    20,0...199,9 Ω 0,1 Ω ±(6% w.m. + 5 digits)
    200...1999 Ω 1 Ω

    Rated voltage: 95...270 V
    Frequency: 45...65 Hz

    Measurement of earth resistance RE with the 3p and 4p method
    Measuring range acc. to IEC 61557 - 5:

    • » 0,50 Ω…1,99 kΩ for test voltage 50 V
    • » 0,56 Ω…1,99 kΩ for test voltage 25 V
    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω ±(2% m.v.. + 3 digits)
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ
    • » test voltage: 25 V or 50 V rms
    • » test current: 20 mA, sinusoidal rms 125 Hz (for fn=50 Hz) and 150 Hz (for fn=60 Hz)
    • » measurement blocked at interference voltage UN > 24 V
    • » maximum measured interference voltage Unmax= 100 V
    • » maximum resistance of auxiliary earth electrodes 50 kΩ
       

    Selective earth resistance measurement with clamp (3p + clamp)
    Measuring range acc. to IEC 61557 - 5: 1 Ω…1,99 kΩ

    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(8% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ
    • » measurement with additional current clamp
    • » interference current measuring range: up to 9,99 A

    Selective earth measurement with two clamps

    Display range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(10% m.v. + 4 digits)
    10,0...99,9 Ω 0,1 Ω
    100...999 Ω ±(20% m.v. + 4 digits)
    • » measurement with transmitting and receiving clamps
    • » interference current measuring range: up to 9,99 A

    Soil resistivity mesurement (ρ)

    Display range Resolution Accuracy
    0,0...99,9 Ωm 0,1 Ωm Depending on accuracy
    of RE measurement
    100...999 Ωm 1 Ωm
    1,00...9,99 Ωm 0,01 kΩm
    10,0...99,9 kΩm 0,1 kΩm
    • » measurement with Wenner’s method
    • » distance settable in metres or feet
    • » distance range: 1...30 m (1...90 feet)

    Phase sequence indication

    • » Phase sequence indication: conforming, non-conforming
    • » Mains voltage range UL-L: 100...440 V (45...65 Hz)
    • » Display of phase-to-phase voltage values

     

    Measurements of RCD parameters (voltage range 95...270 V):

     

     

    RCD tripping test and measurement of tripping time tA (for tA measurement function)

     

    RCD type Current Range Resolution Accuracy
    General and
    short-time
    delay
    0,5*IΔn 0...300 ms

    1 ms

    ± (2% m.v. + 2 digits)

    (for RCD with IΔn=10 mA
    and 0,5xIΔn uncertainty:
    ±(2% m.v. + 3 digits)

    1*IΔn
    2*IΔn 0...150 ms
    5*IΔn 0...40 ms
    Selective 0,5*IΔn 0...500 ms
    1*IΔn
    2*IΔn 0...200 ms
    5*IΔn 0...150 ms

    accuracy of residual current application: for 0,5*IΔn:-8...0% for 1*IΔn, 2*IΔn, 5*IΔn: 0...8%

    Measurement of RCD tripping current IA for sinusoidal residual current (AC type)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 3,3...10,0 mA 0,1 mA 0,3 x IΔ..1,0 x IΔ ± 5%IΔn
    30 mA 9,0...30,0 mA
    100 mA 33...100 mA 1 mA
    300 mA 90...300 mA
    500 mA 150...500 mA
    1000 mA 330...1000 mA

    The measurement can be started from positive or negative half-period of forced leakage current

    Measurement of RCD tripping current IA for unidirectional residual current and unidirectional
    with the 6 mA DC bias (type A)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 3,5...20,0 mA 0,1 mA 0,35 x IΔn..2,0 x IΔn ±10%IΔn
    30 mA 10,5...42,0 mA 0,35 x IΔn..1,4 x IΔn
    100 mA 35,0...140 mA 1 mA
    300 mA 105...420 mA
    500 mA 175...700 mA

    Measurement for positive or negative half-periods of forced leakage current

    Measurement of RCD tripping current IA for direct residual current (type B)

    Rated
    current
    Meas. range Resolution Test current Accuracy
    10 mA 2,0...20,0 mA 0,1 mA 0,4 x IΔn..2,0 x IΔn ±10%IΔn
    30 mA 6...60 mA 1 mA
    100 mA 20...200 mA
    300 mA 60...600 mA
    500 mA 100...1000 mA

    Measurement for positive or negative half-periods of forced leakage current
    IΔn - rated residual current

    Insulation resistance measurements
    Measuring range acc. to IEC 61557 - 2:

    • » for UN = 50 V: 50 kΩ...250 MΩ
    • » for UN = 100 V: 100 kΩ...500 MΩ
    • » for UN = 250 V: 250 kΩ...999 MΩ
    • » for UN = 500 V: 500 kΩ...2 GΩ
    • » for UN = 1000 V: 1,000 MΩ...9,99 GΩ
    Display range*) Resolution Accuracy
    0...1999 kΩ 1 kΩ ±(3% m.v. + 8 digits)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...999 MΩ 1 MΩ
    1,00...9,99 MΩ 0,01 GΩ ±(4% m.v. + 6 digits)

    *) not greater than measuring range for given voltage

    Low-voltage measurement of resistance and circuit continuity
    Measurement of protective conductor continuity with the ±200 mA current

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 digits)
    20,0...199,9 Ω 0,1 Ω
    200...400 Ω 1 Ω
    • » voltage on open terminals: 4…9 V
    • » output current at R < 2 Ω: min. 200 mA
    • » autocalibration of test leads
    • » measurements for both current polarities

    Illuminance measurement

    Range Resolution Accuracy
    0,1...99,9 lx 0,1 lx ±(5% m.v. + 2 digits)
    100...999 lx 1 lx
    1,00...9,99 klx 0,01 lx
    10,0...19,9 klx 0,1 lx

    - - measurement in luxes (lx) or feet-candles (fc)

     

    ANALYSIS AND RECORDING OF SINGLE-PHASE SYSTEM

    • » Voltage measurement ULN: 0...500 V
    • » Frequency range of measured voltages: 45,0...65,0 Hz
    • » Frequency measurement range for 50...500 V voltages: 45,0...65,0 Hz (basic uncertainty max. ± 0,1% m.v. + 1 digit)
    • » cosφ measurement: 0,00...1,00 (resolution 0,01)
    • » Measurement and recording in single-phase system

     

    Current measurement (True RMS)

    Clamps Range Resolution Accuracy*
    C-3, C-6 0,0...99,9 mA 0,1 mA ±(5% m.v. + 3 digits)
    100...999 mA 1 mA
    C-3,C-6
    F-1, F-2, F-3
    1,00...9,99 A 0,01 A ±(5% m.v. + 5 digits)
    (C-3, C-6)
    ±(0,1% In + 2 digits)
    (F-1, F-2, F-3)
    10,0...99,9 A 0,1 A
    100...999 A 1 A
    F-1, F-2, F-3 1,00...3,00 kA 0,01 kA

    * the accuracy of current clamps must also be taken into account

    Measurement of active power P, reactive power Q, apparent power S and cosφ

    Range
    [W], [VA], [var]
    Resolution
    [W], [VA], [var]
    Accuracy*
    0...999 1 ±(7% m.v. + 3 digits)
    1,00...9,99 k 0,01 k
    10,0...99,9 k 0,1 k ±(7% m.v. + 5 digits)
    100...999 k 1 k
    1,00...1,50 M 0,01 M
    • » voltage range: 0…500 V
    • » current range: 0...1000 A (3000 A)
    • » mains rated frequency fn: 50 Hz, 60 Hz
       

    Voltage harmonics measurement

    Range Resolution Nr harm. Accuracy
    0,0...500 V 0,1 (1*) V 1,2,...15 ±(5% m.v. + 3 digits)
    16,...40 ±(5% m.v. + 10 digits)
    • in addition display of h02...h40 values as percent of h01 (up to 999%)

    *) from 300 V to 500 V

    THD (in relation to the 1 st harmonics)

        Resolution Accuracy
    THD-F voltage
    (h = 2…40)
    0,0…999,9%
    for URMS ≥ 1% Unom
     
    0,1% ±5%
    THD-F current
    (h = 2...40)
    0,0…999,9%
    for IRMS ≥ 1% Inom
    0,1% ±5%

     

    NOTE: “m.v.” means “ measured value”

    The instruments conforms to:

    • » EN 61010 - 1 (general safety requirements)
    • » EN 61010 - 031 (detailed safety requirements)
    • » EN 61326 (electromagnetic compatibility)
    • » EN 61557 - 10 (requirements for combined instruments)
    • » IEC 60364 - 6-61 / HD 60364 - 6 (measurements - verification)
    • » IEC 60364 - 4-41 / HD 60364 - 4-41 (measurements – protection against electric shock)
    • » EN 04700 (measurements – acceptance tests)
    • » EN 12464 (lighting of work places)
    • » DIN VDE 0100
    • » DIN VDE 0413
    • » BS 7671


MPI-525

    Description

    • Possible measurements

      Short-circuit loop measurement:

      • » impedance measurement with 23 A current (44 A phase-to-phase) - short-circuit resistor R=10,
      • » measurement range: 95...440 V, frequency 45...65 Hz,

      Short-circuit loop measurement with resolution 0,01, in distribution network without tiggering RCD (In30 mA):

      • » automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
      • » additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.

      Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).

      Measurement of insulation resistance:

      • » with test voltage 250 V, 500 V, 1000 V, 2500 V,
      • » measurement range up to 10G,
      • » automatic discharging after measurement,
      • » automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
      • » acoustic signals in 5 sec intervals for insulation resistance characteristic,
      • » elapsing T1, T2, T3 times (0...600 s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
      • » safety measurement - protection against overvoltage.

      Measurement of earthing resistance.

      Bi-directional testing of PE wire continuity using 200 mA current.

      • » Autocalibration of test leads.

      Phase sequence testing.

      Memory is divided into 10 memory banks each of them containing 99 memory cells.

      Battery charge indicator.

      AUTO-OFF function.

      USB interface.

      MPI-525 is equipment to perform complete test and verify on electrical installations according to the most common safety standards (IEC 61557, VDE 0100, BS7671).

    Specification

  • Possible measurements

    • » Short-circuit loop measurement:
      -impedance measurement with 23 A current (44 A phase-to-phase) - short-circuit resistor R=10 Ω,
      - measurement range: 95...440 V, frequency 45...65 Hz,
    • » Short-circuit loop measurement with resolution 0,01 Ω, in distribution network without tiggering RCD (IΔn≥30 mA):
      - automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
      - additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.
    • » Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).
    • » Measurement of insulation resistance:
      - with test voltage 250 V, 500 V, 1000 V, 2500 V,
      - measurement range up to 10 GΩ,
      - automatic discharging after measurement,
      - automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
      - acoustic signals in 5 sec intervals for insulation resistance characteristic,
      - elapsing T1, T2, T3 times (0...600 s) form measurement of absorption coefficients (DAR, PI or Ab1, Ab2)
      - safety measurement - protection against overvoltage.
    • » Measurement of earthing resistance.
    • » Bi-directional testing of PE wire continuity using 200 mA current.
      - Autocalibration of test leads.
    • » Phase sequence testing.
    • » Memory is divided into 10 memory banks each of them containing 99 memory cells.
    • » Battery charge indicator.
    • » AUTO-OFF function.
    • » USB interface.

    Rated operational conditions:
    - operation temperature 0...+50°C

    Electric security:
    - type of insulation: double, according to PN-EN 61010 - 1and IEC 61557, EMC
    - measurement category: IV 300 V acc. to PN-EN 61010 - 1
    - protection class acc. to PN-EN 60529: IP54

    Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
    Measurement using 23/40 A current measurement range in accordance with
    IEC 61557: 0,13...1999,9 Ω
    (for 1,2 m lead):

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(5% m.v + 3 dgt)
    20,0...199,9 Ω 0,1 Ω
    200...1999 Ω 1 Ω

    rated voltage: 95...270 V (forZL-PE i ZL-N) and 95...440 V (for ZL-L)
    frequency: 45...65 Hz

    Short-circuit loop impedance measurement ZL-PE RCD 
    Measurement using 15 mA current measurement range in accordance with
    IEC 61557: 0,50...1999,9 Ω

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(6% m.v. + 10 dgt)
    20,0...199,9 Ω 0,1 Ω ±(6% m.v + 5 dgt)
    200...1999 Ω 1 Ω

    rated voltage: 95...270 V
    frequency: 45...65 Hz

    Measurement of earthing RE
    Rated voltage in accordance with IEC 61557 - 5: 0,5...1999 Ω

    Range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 dgt)
    10,0...99,9 Ω 0,1 Ω ±(2% m.v. + 3 dgt)
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ

     

    Insulation resistance measurement
    Measurement range in accordance with IEC 61557 - 2:
    - for UN = 50 V: 50 kΩ...250 MΩ
    - for UN = 100 V: 100 kΩ...500 MΩ
    - for UN = 250 V: 250 kΩ...1 GΩ
    - for UN = 500 V: 500 kΩ...2 GΩ
    - for UN = 1000 V: 1 MΩ...3 GΩ
    - for UN = 2500 V: 2,5 MΩ...9,99 GΩ

     

    Range*) Resolution Accuracy
    0...1999 kΩ 1 kΩ ±(3% m.v. + 8 dgt)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...999 MΩ 1 MΩ
    1,00...3,00 GΩ 0,01 GΩ ±(4% m.v. + 6 dgt)
    1,00...9,99 GΩ 0,1 GΩ

     

     

    *) limited to measurement range.
    - with UNI-Schuko additional error ±2%.
     

    Phase sequence
    - phase sequence indicator: forward, reverse
    - mains voltage range UL-L: 100...440 V (45…65 Hz) UL-L: 100...440 V (45...65 Hz)
    - display of phase-to-phase voltages

    Low voltage test of the circuit and insulation continuity
    Test of PE wire continuity using a ±200 mA current

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 dgt)
    20,0...199,9 Ω 0,1 Ω
    200...400 Ω 1

    - Voltage on open terminals: 4…9 V
    - Test current at R<2 Ω: min. 200 mA at rated battery voltage
    - Autocalibration of test leads
    - Measurements for both polarizations of the current

    RCD trigger and response time test tA (for tA mode)
    Measurement ranges in accordance with IEC 61557: 0 ms ... up to the upper bound of the displayed value

    Breaker
    Type
    Test
    Current
    Multiplier
    Measurement
    Range
    Resolution Accuracy
    Standard 0,5*IΔn 0...300 ms

    1 ms

    ± (2% m.v + 2 dgt)

     

    1*IΔn
    2*IΔn 0...150 ms
    5*IΔn 0...40 ms
    Selective 0,5*IΔn 0...500 ms
    1*IΔn
    2*IΔn 0...200 ms
    5*IΔn 0...150 ms

    Precision of the differential current: for 0,5*IΔn:-8...0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0...8%

    Measurement of the RCD triggering current (IA) for sine waveform testing current

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 3,3...10,0 mA 0,1 mA 0,3xIΔ..1,0xIΔ ± 5%IΔn
    30 mA 9,0...30,0 mA
    100 mA 33...100 mA 1 mA
    300 mA 90...300 mA
    500 mA 150...500 mA
    1000 mA 330...1000 mA 1 mA

    It is possible to start the measurement from the positive or negative half of the forced leaking current

    Measurement of the RDC triggering current (IA ) for a unidirectional half period sine
    waveform test current with a 6 mA direct current offset

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 4...20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
    30 mA 12,0...42,0 mA 0,4xIΔn..1,4xIΔn
    100 mA 40,0...140 mA 1 mA
    300 mA 120...420 mA
    500 mA 200...700 mA

    a measurement is possible for a positive or negative forced leakage current

    Measurement of the RCD triggering current (IA ) for direct testing current

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 4,0...20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
    30 mA 12,0...60,0 mA 1 mA
    100 mA 40...200 mA
    300 mA 120...600 mA
    500 mA 200...1000 mA

    a measurement is possible for a positive or negative forced leakage current

    „m.v.” measured value.



MPI-520

    Description

    • The MPI-520 multifunction meter is dedicated to perform diagnosis of electrical installation according to IEC 61557 standards. Digital meter MPI-520 is designed to measure impedance of a short cicuit loop also without triggering RCD, parameters of RCD, insulation resistance, earthing resistance, continuity and also for phase sequence testing. Furthermore to measure and logging of AC voltage and current, frequency and power.
      Wide range of standard accessories enable to perform all necessary measurements and safety test. Highly professional portable multifunction meter with memory of measured parameters.
    • MPI-520 is equipment to perform complete test and verify on electrical installations according to the most common safety standards (IEC 61557, VDE 0100, BS7671).

    Specification

  • Possible measurements:

    Short-circuit loop measurement:

    • » impedance measurement with 23 A current (44 A phase-to-phase) - short-circuit resistor R=10 Ω,
    • » measurement range: 95...440 V, frequency 45...65 Hz,

    Short-circuit loop measurement with resolution 0,01 Ω, in distribution network without tiggering RCD (IΔn≥30 mA):

    • » automatic calculation of short-circuit, detection of phase voltage and phase-to-phase voltage,
    • » additional UNI-Schuko plug for automatic measurement, AGT adapter for 3 phase network measurement.

    Testing of general and selective RCD with the rated differential current of 10,30,100,300,500 and 1000 mA. (Type AC, A and B).

    Measurement of insulation resistance:

    • » with test voltage 250 V, 500 V, 1000 V,
    • » measurement range up to 3 GΩ,
    • » UNI-Schuko plug for insulation measurement,
    • » automatic discharging after measurement,
    • » automatic measurement of all resistences in 3,4,5-wire cables using optional adapter AUTO-ISO,
    • » acoustic signals in 5 sec intervals for insulation resistance characteristic,
    • » safety measurement - protection against overvoltage.

    Measurement of earthing resistance.

    Bi-directional testing of PE wire continuity using 200 mA current.

    • » Autocalibration of test leads.

    Phase sequence testing.

    Memory is divided into 10 memory banks each of them containing 99 memory cells.

    Battery charge indicator.

    AUTO-OFF function.

    USB interface.

    Short-circuit loop impedance measurement ZL-PE, ZL-N, ZL-L
    Measurement using 23/40 A current measurement range in accordance with IEC 61557: 0,13...1999,9 Ω
    (for 1,2 m lead ):

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(5% m.v. + 3 dgt)
    20,0...199,9 Ω 0,1 Ω
    200...1999 Ω 1 Ω

    rated voltage: 95...270 V (for ZL-PE i ZL-N) and 95...440 V (for ZL-L)
    frequency: 45...65 Hz

    Short-circuit loop impedance measurement ZL-PERCD 
    Measurement using 15 mA current measurement range in accordance with
    IEC 61557: 0,50...1999,9 Ω

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(6% m.v. + 10 dgt)
    20,0...199,9 Ω 0,1 Ω ±(6% m.v. + 5 dgt)
    200...1999 Ω 1 Ω

    rated voltage: 95...270 V
    frequency: 45...65 Hz

    Measurement of earthing RE 
    Rated voltage in accordance with IEC 61557 - 5:

    • » 0,5 Ω…1,99 kΩ for 50 V
    • » 0,56 Ω…1,99 kΩ for 25 V
    Range Resolution Accuracy
    0,00...9,99 Ω 0,01 Ω ±(2% m.v. + 4 dgt)
    10,0...99,9 Ω 0,1 Ω ±(2% m.v. + 3 dgt)
    100...999 Ω 1 Ω
    1,00...1,99 kΩ 0,01 kΩ

     

    Insulation resistance measurement
    Measurement range in accordance with IEC 61557 - 2:

     

    • » for UN = 50 V: 50 kΩ...250 MΩ
    • » for UN = 100 V: 100 kΩ...500 MΩ
    • » for UN = 250 V: 250 kΩ...1 GΩ
    • » for UN = 500 V: 500 kΩ...2 GΩ
    • » for UN = 1000 V: 1 MΩ...3 GΩ
    Display range*) Resolution Accuracy**)
    0...1999 kΩ 1 kΩ ±(3% m.v. + 8 dgt)
    2,00...19,99 MΩ 0,01 MΩ
    20,0...199,9 MΩ 0,1 MΩ
    200...999 MΩ 1 MΩ
    1,00...3,00 GΩ 0,01 GΩ ±(4% m.v. + 6 dgt)

    *) limited to measurement range.
    **) with UNI-Schuko additional error ±2%.

    Phase sequence

    • » phase sequence indicator: forward, reverse
    • » mains voltage range UL-L: 100...440 V (45…65 Hz) UL-L: 100...440 V (45...65 Hz)
    • » display of pase-to-phase voltages

    Measurement of the active P, passive Q and apparent S power and cosφ

    • » Range of voltages ULN: 0...440 V
    • » Nominal frequency of the network: 45...65 Hz
    • » frequency measurement for voltage 50...440 V in range 45,0...65,0 Hz (accuracy max. ± 0,1%m.v. + 1 digit)

    - measurement cosφ: 0,00...1,00 (resolution 0,01)

    Low voltage test of the circuit and insulation continuity
    Test of PE wire continuity using a ±200 mA current

    Range Resolution Accuracy
    0,00...19,99 Ω 0,01 Ω ±(2% m.v. + 3 dgt)
    20,0...199,9 Ω 0,1 Ω
    200...400 Ω 1

    Voltage on open terminals: 4…9 V
    Test current at R<2 Ω: min. 200 mA at rated battery voltage
    Autocalibration of test leads
    Measurements for both polarizations of the current

    RCD trigger and response time test tA (for tA mode)Measurement ranges
    in accordance with IEC 61557: 0 ms ... up to the upper bound of the displayed value

    Breaker Type Test Current
    Multiplier
    Measurement
    Range
    Resolution Accuracy
    Standard 0,5*IΔn 0...300 ms

    1 ms

    ± (2% m.v. + 2 dgt)

    1*IΔn
    2*IΔn 0...150 ms
    5*IΔn 0...40 ms
    Selective 0,5*IΔn 0...500 ms
    1*IΔn
    2*IΔn 0...200 ms
    5*IΔn 0...150 ms

    Precision of the differential current: for 0,5*IΔn:-8...0% dla 1*IΔn, 2*IΔn, 5*IΔn: 0...8%

    Measurement of the RCD triggering current (IA) for sine waveform testing current

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 3,3...10,0 mA 0,1 mA 0,3xIΔ..1,0xIΔ ± 5%IΔn
    30 mA 9,0...30,0 mA
    100 mA 33...100 mA 1 mA
    300 mA 90...300 mA
    500 mA 150...500 mA
    1000 mA 330...1000 mA 1 mA

    It is possible to start the measurement from the positive or negative half of the forced leaking current

    Measurement of the RDC triggering current (IA ) for a unidirectional half period sine
    waveform test current with a 6 mA direct current offset

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 4...20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
    30 mA 12,0...42,0 mA 0,4xIΔn..1,4xIΔn
    100 mA 40,0...140 mA 1 mA
    300 mA 120...420 mA
    500 mA 200...700 mA
    • » a measurement is possible for a positive or negative forced leakage current

    Measurement of the RCD triggering current (IA ) for direct testing current

    Selected
    Current
    Range Resolution Test
    Current
    Accuracy
    10 mA 4,0...20,0 mA 0,1 mA 0,4xIΔn..2,0xIΔn ±10%IΔn
    30 mA 12,0...60,0 mA 1 mA
    100 mA 40...200 mA
    300 mA 120...600 mA
    500 mA 200...1000 mA
    • » a measurement is possible for a positive or negative forced leakage current

    „m.v.” measured value.